1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
FA 8
Maximum speed for condenser fan in Chiller mode.
To set the maximim fan speed percentage value (30..100%), it is
related to the fan power supply.
30 100 %
FA 9 Proportional speed control FA01 = 4
Temperature or pressure limit to enable the minimum speed FA 7
ON/OFF regulation FA01 = 2 / 3
SETpoint step 1
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 10
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the maximum speed FA 8
ON/OFF regulation FA01 = 2 / 3
SETpoint step 2
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 11
Proportional speed control FA01 = 4
Proportional band for condenser fan control in chiller
To set the temperature/pressure differential between the minimum
and the maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2 / 3
Differential step circuit 1
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 12
Proportional speed control FA01 = 4
CUT-OFF differential in chiller. To set a temperature/pressure
differential to stop the fan.
ON/OFF regulation FA01 = 2 / 3
Differential step circuit 2
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 13
Over ride CUT- OFF in chiller.
To set a temperature/pressure differential to keep the minimum fan
speed.
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 14
CUT-OFF time delay.
To set a time delay before activating the CUT-OFF function after the
fan start-up.
If after the compressor start-up the proportional regulator requires to
turn off the fan (cut-off) and FA140, the fan is on at the minimum
speed for the time set in this parameter. If FA14=0 the function is
disabled.
0 250 Sec
FA 15
Night speed in chiller. To set the maximum fan speed percentage
value (30..100%), it is related to the fan power supply.
30 100 %
Fan in Heat pump mode
FA 16
Minimum speed for condenser fan in Heat Pump mode.
To set the minimum fan speed percentage value (30..100%), it is
related to the fan power supply.
30 100 %
FA 17
Maximum speed for condenser fan in Heat Pump mode.
To set the maximum fan speed percentage value (30..100%), it is
related to the fan power supply.
30 100 %
FA 18
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the minimum speed FA16
ON/OFF regulation FA01 = 2/3
SETpoint step 1
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 19
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the maximum speed FA17
ON/OFF regulation FA01 = 2/3
SETpoint step 2
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 20
Proportional speed control FA01 = 4
Proportional band for condenser fan control in heat pump
To set the temperature/pressure differential between the minimum
and the maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit 1
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the dixell IC200CX Series and is the answer not in the manual?

dixell IC200CX Series Specifications

General IconGeneral
Branddixell
ModelIC200CX Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals