4-15
CH 4/ Instrument Settings
Factory default
settings
Dranetz-BMI has set the default values for the various parameters of the PX5.
Current Probes:
TR2500/TR2500A for A, B, C; TR2510/TR2510A for D
Scale Factors:
1:1 for V and I, channels A, B, C, D
Circuit Type:
three phase wye
Mode of Operation:
monitor
Nominal Value:
measured V, I, frequency
Monitoring Mode:
Standard Power Quality
Advanced Operations:
individual limit setups
Transient Limits:
intantaneous peak = 3X nominal V, waveshape = 10% ,
rms dev = 10% , fast transient = 3X nominal V, none for I
RMS Variation Limits:
10% Very Low, 90% Low, 110% High for voltage; none for
current
Journal Limit:
journalling By Time for the various parameters
Triggers:
all V trigger; all V and I channels
Journal Interval
Power Values:
Power Values Interval: 15 minutes
Waveform Snapshot: OFF
Demand and Energy:
Demand Sub-Interval: 5 minutes
Sub-Intervals per Interval: 3
Harmonics Journal Interval:
15 minutes
Flicker:
Pst (Short Term) Interval: 10 minutes
Plt (Long Term) Interval: 2 hours
Site Name:
Power Xplorer Site
Clock Type:
Analog
Date:
mm/dd/yy
Language:
English
Display
Backlight Timer: 1 minute
Contrast:
70%
Password Protect:
OFF