89
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Table 89-1:
Troubleshooting guide (continued)
Gas-to-steam (GTS) humidifier issues
Issue Possible causes Actions
Alert: Blocked flue Blocked flue sensor is open Check venting system for obstructions.
Check air line to flue switch for obstructions.
Windy conditions cause downdrafts in venting system. Install
a high wind vent cap or isolate as recommended by local
codes.
Alert: Gas valve [number]
fault
Failed ignition module
Miswired gas valve
Check ignition module. Replace if necessary.
Check gas valve wiring.
Alert: Burner [number] fault No gas supply to unit Verify that gas service valve is on and receiving minimum
pressure to manifold per rating plate.
Gas valve is off or there is no power to the
valve
Check for 24 VAC from the ignition module to the gas valve.
Check that gas valve plug is seated properly.
Gas valve outlet pressure is too low Verify outlet pressure is set per rating plate.
Blower inlet is dirty or obstructed Clean inlet and check for obstructions.
Flame sensor not sensing flame Check flame sensor wiring.
Check polarity at incoming power. Switch if necessary.
Stray fiber from burner touching flame sensor. Use a
screwdriver to gently push down fibers near flame sensor.
Flame sensor is cracked. Replace.
Polarity reversed at power block Check polarity.
Alert:
Ignition module [number] fault
Ignition sequence engaged without power to
gas valve
Verify ignition sequence.
Replace ignition module.
Gas valve/ignite/sensing electrode is out of
sequence
Verify wire connections to gas valve, ignitor, and flame
sensing rod.
Alert:
Blower [number] fault
The blower is incorrectly wired, or the
blower failed to meet demand speed
Check for proper blower wiring.
Replace blower.
Alert:
No power vent airflow
The power venter air flow switch is open Check for proper power vent wiring.
Repair or replace power venter.
Alert:
Flue temperature switch
Flue temperature is too high
Tank is not full
Unit automatically shuts off and cools down. The unit will
automatically restart when flue temperatures return to
normal.
Alert:
Tank temperature switch
Flue temperature is too high
Tank is not full
Excessive inlet water temperature (over 90°F [32°C]).
Check if water supply line strainer is plugged.
Clean scale from tank and heat exchanger.
Check supply water pressure. Provide supply water pressure
as specified on unit.
Alert:
Flue or tank overtemp cutout
Flue temperature is too high
Excessive inlet water temperature (over
90°F [32°C]).
Unit automatically shuts off and cools down. The unit will
automatically restart when flue temperatures return to
normal.
Tank is not full Check if water supply line strainer is plugged.
Check supply water pressure. Provide supply water pressure
as specified on unit.
Excessive scale for tank and heat
exchanger
Clean scale from tank and heat exchanger.
Alert:
Flue sensor out of range
Signal outside of 4-20mA Check P4 voltage from CS1 to ground (2-10vdc)
Replace transmitter if no voltage output
Check voltage on P6 from 21vdc to ground is 21vdc. If not,
re-check terminals for all field connections.
Troubleshooting guide
TROUBLESHOOTING