78
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Multiple-tank operation
CHANGING A PRIORITY GROUP
To change a priority group, go to the Settings menu to access Multi-tank setup/
Tank priority group.
To add a tank to a multi-tank system:
1. Verify that the new tank has the correct tank designator. Change, if
necessary, before wiring in Step 2.
2. Connect wiring of new tank.
3. The master controller automatically adds the new tank’s capacity into the
total system capacity.
To permanently remove a tank from a multi-tank system:
1. Disconnect control board wiring (location P8) of the tank being removed.
2. Reset system capacity from the Multi-tank Settings menu. The controller will
automatically calculate the new system capacity.
Important:
• Each tank in a multi-tank system must have a unique tank designator (A, B,
C ... P). Duplicate tank designations will cause multi-tank mode to operate
incorrectly.
• Each Vapor-logic board ships with a network IP address of 192.168.1.195.
When installing on an Ethernet network, assign each board a unique IP
address to avoid conflict with other devices on the network.
OTHER SYSTEM PARAMETERS AND INTEROPERABILITY
General system parameters are set the same as for stand-alone tank/controller.
See the Setup section of this manual for instructions.
MULTI-TANK OPERATION WITH WEB INTERFACE
If you plan to use the Web interface for multi-tank operation, the web interface
must first be configured, see "Web interface communication" on Page 21.
OPERATION