DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 53
Table 53-1:
Program operating mode (continued)
Mode
Program
variable
Definition
Default
display
Alternate
display
Range Increment Variable type
Program
(continued)
FL.PU
Fill valve pulsed. If function is active, fill valve
will open for 3 seconds and close for 7 seconds
repeatedly, until water level in steam cylinder is
adequate:
oF function not active
on function active
oF on Variable
r1
r2
Relay 1 or Relay 2:
SE Collective message without E1
b Relay switches during steam operation
S Collective message (displayed if any E1-E5)
E1 Cylinder service message (displays at end of
cylinder life)
E2 Over current (displays if unit exceeds 140% of
nominal current and shuts unit down)
E3 No water (displays after 30 minutes if no water in
cylinder and shuts unit down)
E4 Uncoded replacement processor board
E5 Service setpoint reached
r1.SE
r2.E1
r1. b
r1. S
r1.E1
r1.E2
r1.E3
r1.E4
r1.E5
Variable
noE1
No E1 message:
oF E1 message will be displayed
on E1 message is suppressed
oF on Variable
FOAM
Setting of the anti-foam program:
oF function not active
on function active
oF on Variable
AdrS Address of unit to be controlled by a PC 01 00-29 01 Variable
o.SEt
Original settings (reset code: 91). All programmed
parameters are reset to factory default settings. While
in o.SEt, press the SET button until 91 is displayed.
Factory default settings when o.SEt is displayed
again.
Program reset
Operating modes (continued)