5.5 MODULES CONNECTION
5.5.1 DSEWEBNET
This page configures how the DSEGateway
®
communicates wih the DSEWebNet® server.
NOTE: A maximum of 5 connections can be made in the DSE WebNet page. That is a
maximum of 5 controllers are supported on DSEWebNet
®
by each DSEGateway
®
.
NOTE: If a Port is used in the Modbus section, it cannot be used to create a DSEWebNet®
Connection.
NOTE: RS232 is a single master, single slave system. This means that only one entry
must be created for RS232 in the Port column.
NOTE: USB is a single master, single slave system. This means that only one entry must
be created for USB in the Port column.
Parameters described overleaf.
Connectivity
LED indicates
green when this
connection is
communicating
correctly.