EasyManua.ls Logo

DSE DSE890 - MODBUS CONFIGURATION

DSE DSE890
53 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setup
Page 47 of 53
057-165 ISSUE: 9.0
5.5.3 MODBUS
NOTE: This section is only used when setting up the DSEGateway
®
to operate as a
communications protocol convertor. This section must be left with no entries if using the
DSEGateway
®
with the DSEWebNet® system.
NOTE: A maximum of 5 connections can be made in the Modbus page. That is a maximum
of 5 controllers are supported for protocol conversion by each DSEGateway
®
.
NOTE: Ports used in the Modbus section are dedicated to protocol conversion and cannot
be used to connect a module to the DSEWebNet® system.
This page is used to configure the DSEGateway
®
as a Modbus Gateway to allow conversion across
the various ports.
It can be used for example to set USB as a modbus master to connect to any DSE controller fitted
with a USB port and supporting the DSE Configuration Suite SCADA function.
5.5.3.1 SLAVE
These are the settings of the DSEGateway® port this is connected to the monitoring device.
Parameter
Description
ID
Modbus slave address of the selected DSEGateway
®
port
Port
This is the modbus slave port that is connected to the Modbus Master ( for
example PC, Building Managmement System or PLC).
RS232: Connection to the master via RS232. Check specifications of the
master as to whether NULL MODEM (crossover) cable is required,
RS485: Connection to the master via RS4852 and suitable RS485 cable.
Ethernet: Connection to an Ethernet network accessible by the modbus
master.
TCP Port/Serial
Baud
When Port is set to Ethernet TCP port to use for Modbus (usually 502)
When Port is set to RS232/RS485 Baud rate of the selected port.

Table of Contents

Related product manuals