Dungs MPA 5111 - Error from the Extended Functions (0 x40 to 0 x9 F)

Dungs MPA 5111
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41 … 68
40 … 68
Printed in Germany • Edition 02.14 • Nr. 254 722
10 Error overview
MPA 51xx
Error
ID
Internal
error
Error description Possible cause of the error
0x19 not used
0x1A ERROR_SWWD_DURING_INITIALISATION
0x1B ERROR_BUFFEROVERFLOW
0x1C
ERROR_SYNCHRONISATION_DURING_INI-
TIALISATION
0x1D
ERROR_PROCESSORFAILURE ? MPA is inuenced by strong EMC inter-
ferences
0x1E ERROR_SFRREGISTER_STATEBLOCK
... not used
10.3 Error from the extended functions (0x40 to 0x9F)
0x40
ERROR_FANDEFAULTS ? In the curve segment, a fan default is
predened, which is smaller than the mini-
mum speed or higher than the maximum
speed of the fan (P26 or P27).
P26 (min. speed) is 500 U/min but the
speed for modulation degree 0% is set
to 480 rpm. Or P27 (max. speed) is set to
5600 rpm but the pre-aeration B should be
carried out with 5800 rpm.
0x41
ERROR_FAN_DEVIATION ? The number of pulses in the fan feed-
back is set to an incorrect value
? The fan is not suitable for the desired
speed
? The predened tolerance is too low or
the fan controller is not optimised
0x42
ERROR_FAN_NO_FEEDBACK ? The feedback line of the fan is not cor-
rectly connected or is interrupted
? The fan is blocked and does not work
? The fan is not supplied with power or is
defective
0x43 ERROR_TEST_IONISATIONINPUT
0x44
ERROR_CURVECRC16_TEST ? The curve segment was temporarily
changed, for ex. for putting the MPA into
operation, and was not correctly enabled
later
0x45 ERROR_INVALID_MODULATIONDEGREE ? Modulation degree is outside the limits
0x46 not used
0x47 ERROR_INVALID_STEPPEDMOTORTYPE ? Check stepped motor (compare P30)
0x48
ERROR_STEPPEDMOTOR_TOLERANCE_EX-
CEEDED
? The lines to the stepped motor are not
correctly connected or partly interrupted
? The stepped motor is charged with more
than the admissible torque, for example
due to improper mounting of the ap or
pressure impulses.
0x49
ERROR_STEPPEDMOTOR_REFERENCE_
NOT_FOUND
? see error 0x48
0x4A ERROR_STEPPEDMOTOR_NO_REACTION ? see error 0x48
0x4b
ERROR_PARAMETERRECORDSTICK_NOT_
FOUND
? Parameter record activated but not
plugged in the MPA
? Stick defective
? Duration of the standard mode (P70) is
higher than 23 h 59 min and the continu-
ous run is not enabled
? PWM outputs congured to analogue
operation (0..10 V or 4...20 mA) but no suit-
able stick is plugged in.