29 … 68
28 … 68
Printed in Germany • Edition 02.14 • Nr. 254 722
8 Parameters
8.5 P5x - Additional valve
Parameter
P5x
Designation Description Setting
P50 Additional valve:
Activation state
In the state dened here, the output
of the additional valve is activated.
Attention! The actual activation
can take place with a delay in time!
See also P52.
P51 Additional valve: De-
activation state
In the state dened here, the output
of the additional valve is deactivat-
ed.
Attention! The actual deactivation
can take place with a delay in time!
See also P53.
P52 Additional valve:
Time-delayed activa-
tion
Using this parameter, the time-
delayed activation is dened, that
means that the additional valve is
switched on a set time period after
the activation of the state dened in
P50.
Attention! If the duration of the
state is shorter than the dened
delay, the additional valve is only
activated with the start of the sub-
sequent state. For example, if the
state "Pre-aeration A" is set with a
delay in time of 40 seconds (P50
and P52), the pre-aeration time A,
however, (P60) lasts only 30 sec-
onds, the additional valve is al-
ready activated after 30 seconds
when the next state is started (e.g.
"pre-aeration B) and not 40 sec-
onds after the start of the state
"pre-aeration A".
P53 Additional valve:
Time-delayed deacti-
vation
Same function as P52, but with a
delay in time for the switch-o key.