8 Parameters
8.9 P9x - Waiting program
Parameter
P9x
Designation Description Setting
P90 Waiting program:
Restart
attempts
Denes the number of restart at-
tempts after the errors "Lack of
gas on GDWVPS" or "Safety chain
open" until the MPA switches to the
fault switch-o.
The setting 0xFF and 255 means
that an innite number of restart at-
tempts can be carried out without
activating the fault switch-o of the
MPA.
P91 Waiting program:
Duration
Denes the time period after which
the MPA carries out another restart
attempt.
Attention! For the rst restart at-
tempts, the duration can dier from
this setting! See state: "Waiting
program".