EasyManua.ls Logo

Dungs MPA 5111 - P9 x - Waiting Program

Dungs MPA 5111
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35 … 68
34 … 68
Printed in Germany • Edition 02.14 • Nr. 254 722
8 Parameters
8.9 P9x - Waiting program
Parameter
P9x
Designation Description Setting
P90 Waiting program:
Restart
attempts
Denes the number of restart at-
tempts after the errors "Lack of
gas on GDWVPS" or "Safety chain
open" until the MPA switches to the
fault switch-o.
The setting 0xFF and 255 means
that an innite number of restart at-
tempts can be carried out without
activating the fault switch-o of the
MPA.
P91 Waiting program:
Duration
Denes the time period after which
the MPA carries out another restart
attempt.
Attention! For the rst restart at-
tempts, the duration can dier from
this setting! See state: "Waiting
program".

Table of Contents

Related product manuals