EasyManuals Logo

Dungs MPA 5111 User Manual

Dungs MPA 5111
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
31 … 68
30 … 68
Printed in Germany • Edition 02.14 • Nr. 254 722
.
8 Parameters
8.7 P7x - Operation
Parameter
P7x
Designation Description Setting
P70 Duration Standard
mode
Here you can dene whether the
automatic burner control should
carry out a voluntary switch-o. If
yes, dene the operating time (in
minutes)
Typical settings:
0xFFFF = 65535 Continuous op-
eration / no switch-o.
1439 = 23h 59 min intermittent op-
eration.
Also other values are possible, e.g.
60 = switch-o after 1 hour.
Continuous operation ( 24 h) is
only possible using acontinuous
operation stick, see section 8.11
P71 Modulation degree:
new nominal value
This value can be used to dene a
new modulation degree. As soon
as the automatic burner control has
recognised a new value, this param-
eter is reset to 0xFFFF (=65535).
P72 Modulation degree:
Type of modication
Denes the type of modulation de-
gree that is predened for the op-
eration:
Setting 0: Externally, that means
only by means of one of the com-
munication interfaces to a new ab-
solute value
Setting 1: Plus / Minus, that means
via a communication interface to an
absolute value or upwards (plus) or
downwards (minus) relative to the
currently set modulation degree via
the two corresponding hardware
inputs.
Setting 2: By means of a suitable
extension module via an analogue
input to an analogue predened
absolute value with the full range of
values, for example 0 V (0 %) to 10
V (100 %). *1
Setting 3: By means of a suitable
extension module via an analogue
input to an analogue predened
absolute value with a limited range
of values, for example 4 mA (0 %)
to 20mA (100 %). *1
*1: The analog value is accepted as
soon as the detected modication is
> 5 % of the nal value (e.g. > 1 mA
at 4...20 mA). Modications < 5 %
are accepted only after a certain time
(see P74).
Modications between 0% and
+0.5% are considered as "Noise" and
are eliminated.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dungs MPA 5111 and is the answer not in the manual?

Dungs MPA 5111 Specifications

General IconGeneral
BrandDungs
ModelMPA 5111
CategoryControl Unit
LanguageEnglish

Related product manuals