Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F 94
The Set Date and Time DD/MM/YYYY screen allows the internal date and time of the UPS to be set in the day/
month/year format. The date and time information is used for display on the screen and for logging events in
the Event and History Logs. Figure 64 shows the Set Date and Time DD/MM/YYYY screen.
Use the
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-15
Select TIME INTERVAL MONITORED from the Current kW Demand Log Setup screen 2
menu to display the Time Interval Monitored Setup screen. The Time Interval
Monitored Setup screen allows the time duration of the event being monitored to be
changed. Figure 8‐17 shows the Time Interval Monitored Setup screen.
Use the
or pushbuttons to select the character position. Use the or
pushbuttons to change the character value. Once the new value is entered, press the
DONE pushbutton. The Time Interval Monitored Setup Save screen is displayed.
0000
DONE
TIME INTERVAL MONITORED SETUP
Figure 8‐17. Time Interval Monitored Setup Screen
The Time Interval Monitored Setup Save screen lets you save the new time interval,
retry another time interval, or abort the change. Figure 8‐18 shows the Time Interval
Monitored Setup Save screen.
Press SAVE, RETRY, or ABORT. If SAVE or ABORT is pressed, the action is completed,
and the Current kW Demand Log Setup screen 2 displays. If RETRY is pressed, the
Time Interval Monitored Setup screen is redisplayed.
ABORT
SAVE RETRY
0000
TIME INTERVAL MONITORED SETUP
Figure 8‐18. Time Interval Monitored Setup Save Screen
or
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-15
Select TIME INTERVAL MONITORED from the Current kW Demand Log Setup screen 2
menu to display the Time Interval Monitored Setup screen. The Time Interval
Monitored Setup screen allows the time duration of the event being monitored to be
changed. Figure 8‐17 shows the Time Interval Monitored Setup screen.
Use the
or pushbuttons to select the character position. Use the or
pushbuttons to change the character value. Once the new value is entered, press the
DONE pushbutton. The Time Interval Monitored Setup Save screen is displayed.
0000
DONE
TIME INTERVAL MONITORED SETUP
Figure 8‐17. Time Interval Monitored Setup Screen
The Time Interval Monitored Setup Save screen lets you save the new time interval,
retry another time interval, or abort the change. Figure 8‐18 shows the Time Interval
Monitored Setup Save screen.
Press SAVE, RETRY, or ABORT. If SAVE or ABORT is pressed, the action is completed,
and the Current kW Demand Log Setup screen 2 displays. If RETRY is pressed, the
Time Interval Monitored Setup screen is redisplayed.
ABORT
SAVE RETRY
0000
TIME INTERVAL MONITORED SETUP
Figure 8‐18. Time Interval Monitored Setup Save Screen
pushbuttons to highlight the setting to be changed. Use the
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-4
8.2.2 Event Screens
Press the EVENTS pushbutton on the main menu bar or History Menu bar to display a
listing of all system events that are currently active. The most recent event is listed
first. As events clear, they are removed from the Active System Events listing.
Figure 8‐4 shows the Active Events screen.
To scroll through the events, press the
or pushbuttons on the menu bar.
ACTIVE EVENTS
HISTORY
ALARM: INPUT AC UNDERVOLTAGE
ALARM: BYPASS AC UNDER VOLTAGE
NOTICE: BATTERY VOLTAGE LOW
NOTICE: NO SYNC ON
NOTICE: BYPASS NOT AVAILABLE
NOTICE: CONFIGURATION ERROR
Figure 8‐4. Active Events Screen
or
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-4
8.2.2 Event Screens
Press the EVENTS pushbutton on the main menu bar or History Menu bar to display a
listing of all system events that are currently active. The most recent event is listed
first. As events clear, they are removed from the Active System Events listing.
Figure 8‐4 shows the Active Events screen.
To scroll through the events, press the
or pushbuttons on the menu bar.
ACTIVE EVENTS
HISTORY
ALARM: INPUT AC UNDERVOLTAGE
ALARM: BYPASS AC UNDER VOLTAGE
NOTICE: BATTERY VOLTAGE LOW
NOTICE: NO SYNC ON
NOTICE: BYPASS NOT AVAILABLE
NOTICE: CONFIGURATION ERROR
Figure 8‐4. Active Events Screen
pushbuttons to make the
change. When finished making changes, use the
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-15
Select TIME INTERVAL MONITORED from the Current kW Demand Log Setup screen 2
menu to display the Time Interval Monitored Setup screen. The Time Interval
Monitored Setup screen allows the time duration of the event being monitored to be
changed. Figure 8‐17 shows the Time Interval Monitored Setup screen.
Use the
or pushbuttons to select the character position. Use the or
pushbuttons to change the character value. Once the new value is entered, press the
DONE pushbutton. The Time Interval Monitored Setup Save screen is displayed.
0000
DONE
TIME INTERVAL MONITORED SETUP
Figure 8‐17. Time Interval Monitored Setup Screen
The Time Interval Monitored Setup Save screen lets you save the new time interval,
retry another time interval, or abort the change. Figure 8‐18 shows the Time Interval
Monitored Setup Save screen.
Press SAVE, RETRY, or ABORT. If SAVE or ABORT is pressed, the action is completed,
and the Current kW Demand Log Setup screen 2 displays. If RETRY is pressed, the
Time Interval Monitored Setup screen is redisplayed.
ABORT
SAVE RETRY
0000
TIME INTERVAL MONITORED SETUP
Figure 8‐18. Time Interval Monitored Setup Save Screen
or
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-15
Select TIME INTERVAL MONITORED from the Current kW Demand Log Setup screen 2
menu to display the Time Interval Monitored Setup screen. The Time Interval
Monitored Setup screen allows the time duration of the event being monitored to be
changed. Figure 8‐17 shows the Time Interval Monitored Setup screen.
Use the
or pushbuttons to select the character position. Use the or
pushbuttons to change the character value. Once the new value is entered, press the
DONE pushbutton. The Time Interval Monitored Setup Save screen is displayed.
0000
DONE
TIME INTERVAL MONITORED SETUP
Figure 8‐17. Time Interval Monitored Setup Screen
The Time Interval Monitored Setup Save screen lets you save the new time interval,
retry another time interval, or abort the change. Figure 8‐18 shows the Time Interval
Monitored Setup Save screen.
Press SAVE, RETRY, or ABORT. If SAVE or ABORT is pressed, the action is completed,
and the Current kW Demand Log Setup screen 2 displays. If RETRY is pressed, the
Time Interval Monitored Setup screen is redisplayed.
ABORT
SAVE RETRY
0000
TIME INTERVAL MONITORED SETUP
Figure 8‐18. Time Interval Monitored Setup Save Screen
pushbuttons to highlight SAVE and the
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-4
8.2.2 Event Screens
Press the EVENTS pushbutton on the main menu bar or History Menu bar to display a
listing of all system events that are currently active. The most recent event is listed
first. As events clear, they are removed from the Active System Events listing.
Figure 8‐4 shows the Active Events screen.
To scroll through the events, press the
or pushbuttons on the menu bar.
ACTIVE EVENTS
HISTORY
ALARM: INPUT AC UNDERVOLTAGE
ALARM: BYPASS AC UNDER VOLTAGE
NOTICE: BATTERY VOLTAGE LOW
NOTICE: NO SYNC ON
NOTICE: BYPASS NOT AVAILABLE
NOTICE: CONFIGURATION ERROR
Figure 8‐4. Active Events Screen
or
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-4
8.2.2 Event Screens
Press the EVENTS pushbutton on the main menu bar or History Menu bar to display a
listing of all system events that are currently active. The most recent event is listed
first. As events clear, they are removed from the Active System Events listing.
Figure 8‐4 shows the Active Events screen.
To scroll through the events, press the
or pushbuttons on the menu bar.
ACTIVE EVENTS
HISTORY
ALARM: INPUT AC UNDERVOLTAGE
ALARM: BYPASS AC UNDER VOLTAGE
NOTICE: BATTERY VOLTAGE LOW
NOTICE: NO SYNC ON
NOTICE: BYPASS NOT AVAILABLE
NOTICE: CONFIGURATION ERROR
Figure 8‐4. Active Events Screen
pushbuttons to select YES. To complete the save function and return to the System Setup screen, select the
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-3
8.2 Using the Main Menu
The UPS main menu bar allows you to display data in the information area to help you
monitor and control UPS operation. The following menus and options are available:
Menu Option Description
EVENTS Displays the list of Active System Events and a historical log of system events.
METERS Displays performance meters for the system or critical load.
CONTROLS Displays the System Controls screen.
SETUP Allows you to set the display contrast, set the date and time for the time stamp,
configure the UPS serial communication ports, and view the firmware version numbers.
LOAD OFF De-energizes the critical load and powers down the UPS.
Returns to Main Menu and Mimic screen from the Events, Meters, Controls, or Setup
screens. Returns to the main System Setup Level screen from a setup submenu.
8.2.1 Mimic Screen
Figure 8‐3 shows the Main Menu and Mimic screen. To select the Mimic screen from
the Events, Meters, Controls, or Setup screens, press the
pushbutton on the
current menu bar.
The Mimic screen shows the internal components of the UPS cabinet and a real‐time
graphical representation of the operating status of the system.
TIME: 11 : 35 : 43 DATE: 02 / 25 / 2004
CONTROLS LOAD OFF
METERSEVENTS SETUP
OUTPUT
BATT
UPS
INPUT
STSW
BYPASS
Figure 8‐3. Main Menu and Mimic Screen (Normal Mode)
pushbutton.
FFiigguurree 6644.. SSeett DDaattee aanndd TTiimmee DDDD//MMMM//YYYYYYYY SSccrreeeenn
DATE MONTH YEAR HOUR MINUTE SAVE
27 02 2004 15 42 YES
SET DATE AND TIME DD/MM/YYYY
Using the Control Panel