POWER WIRING INSTALLATION NOTES
091505 A
164201604-5
6 of 15
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
11.Per NEC article 300‐20(a), all three‐phase conductors must be run in the same conduit.
Neutral and ground must be run in the same conduit as the phase conductors.
12.Conduit is sized to accommodate one neutral conductor the same size as the phase
conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized
neutral conductor are to be installed, check the size of the conduit needed to
accommodate the extra wire or size and use that conduit size in place of the conduit size
listed in Table J. All Eaton 9390 products can accommodate a double size neutral.
13.Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW‐2, TW, THW,
THHW, THW‐2.
Table J. Power Cable Conduit Requirements
UPS Model Voltage Terminal
Number of
Wires in
Conduit
Minimum Conduit
Trade Size (inches)
Number of
Conduits
Eaton
9390-120/100
and
9390-160/100
208/220
AC
AC Input to UPS
(A, B, C, Gnd)
4 2‐1/2 2
AC Input to Bypass
(A, B, C, Neut, Gnd)
5 2‐1/2 2
Output
(A, B, C, Neut, Gnd)
5 2‐1/2 2
DC
Battery
(Positive), (Negative), Gnd
5 2 1
Eaton
9390-120/100
and
9390-160/100
480
AC
AC Input to UPS
(A, B, C, Gnd)
4 2‐1/2 1
AC Input to Bypass
(A, B, C, Neut, Gnd)
5 2‐1/2 1
Output
(A, B, C, Neut, Gnd)
5 2‐1/2 1
DC
Battery
(Positive), (Negative), Gnd
5 2 1
Eaton
9390-120/120
and
9390-160/120
208/220
AC
AC Input to UPS
(A, B, C, Gnd)
4 2‐1/2 2
AC Input to Bypass
(A, B, C, Neut, Gnd)
5 2‐1/2 2
Output
(A, B, C, Neut, Gnd)
5 2‐1/2 2
DC
Battery
(Positive), (Negative), Gnd
5 2 1
Eaton
9390-120/120
and
9390-160/120
480
AC
AC Input to UPS
(A, B, C, Gnd)
4 1‐1/2 2
AC Input to Bypass
(A, B, C, Neut, Gnd)
5 1‐1/2 2
Output
(A, B, C, Neut, Gnd)
5 1‐1/2 2
DC
Battery
(Positive), (Negative), Gnd
5 2 1