POWER WIRING INSTALLATION NOTES
C
164201604-5
011509
7 of 15
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
Table J. Power Cable Conduit Requirements (Cont'd)
UPS Model Voltage Terminal
Number of
Wires in
Conduit
Minimum Conduit
Trade Size (inches)
Number of
Conduits
Eaton
9390-160/160
208/220
AC
AC Input to UPS
(A, B, C, Gnd)
4 3‐1/2 2
AC Input to Bypass
(A, B, C, Neut, Gnd)
5 3‐1/2 2
Output
(A, B, C, Neut, Gnd)
5 3‐1/2 2
DC
Battery
(Positive), (Negative), Gnd
5 2‐1/2 1
Eaton
9390-160/160
480
AC
AC Input to UPS
(A, B, C, Gnd)
4 2 2
AC Input to Bypass
(A, B, C, Neut, Gnd)
5 2 2
Output
(A, B, C, Neut, Gnd)
5 2 2
DC
Battery
(Positive), (Negative), Gnd
5 2‐1/2 1
Eaton
9390-160/100
380/400/
415
AC
AC Input to UPS
(A, B, C, Gnd)
4 2‐1/2 1
AC Input to Bypass
(A, B, C, Neut, Gnd)
5 2‐1/2 1
Output
(A, B, C, Neut, Gnd)
5 2‐1/2 1
DC
Battery
(Positive), (Negative), Gnd
5 2 1
Eaton
9390-160/120
380/400/
415
AC
AC Input to UPS
(A, B, C, Gnd)
4 2‐1/2 2
AC Input to Bypass
(A, B, C, Neut, Gnd)
5 2‐1/2 2
Output
(A, B, C, Neut, Gnd)
5 2‐1/2 2
DC
Battery
(Positive), (Negative), Gnd
5 2 1
Eaton
9390-160/160
380/400/
415
AC
AC Input to UPS
(A, B, C, Gnd)
4 2‐1/2 2
AC Input to Bypass
(A, B, C, Neut, Gnd)
5 2‐1/2 2
Output
(A, B, C, Neut, Gnd)
5 2‐1/2 2
DC
Battery
(Positive), (Negative), Gnd
5 2 1