159 Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F
FFiigguurree 8833.. 116644220011660044--55 PPoowweerr WWiirriinngg IInnssttaallllaattiioonn NNootteess ((CCoonnttiinnuueedd))
14. External overcurrent protection is not provided by this product, but is required by codes.
Refer to Table E through Table G for wiring requirements. If an output lockable disconnect
is required, it is to be supplied by the user.
15. Table K lists the maximum rating for input circuit breakers. When wiring a singlefeed input,
the rating requirements for the input circuit breakers are superceded by the ratings listed in
Table L.
Table K. Maximum Input Circuit Breaker Ratings
UPS Model
Input Voltage Rating
208V/220V 380V 400V 415V 480V
Eaton 9390-120/100
Eaton 9390-160/100
80% Rated 450A 225A 225A 200A 200A
100% Rated 350A 200A 175A 175A 150A
Eaton 9390-120/120
Eaton 9390-160/120
80% Rated 500A 300A 250A 250A 225A
100% Rated 450A 225A 200A 200A 175A
Eaton 9390-160/160
80% Rated 700A 350A 350A 350A 300A
100% Rated 600A 300A 300A 300A 250A
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from
Table K in accordance with the NEC, ANSI/NFPA 70.
16. Source protection for the AC input to bypass should be treated as if supplying a 160 kVA
threephase transformer, to allow for inrush current if an Integrated Distribution Cabinet
(IDC) with a transformer is installed. Bypass input wiring and bypass input breaker rating
should be treated as if supplying a 160 kVA load, regardless of the rating of the UPS.
17. The linetoline unbalanced output capability of the UPS is limited only by the full load
per phase current values for AC output to critical load shown in Table E through Table G.
The recommended linetoline load unbalance is 50% or less.
18. Bypass and output overcurrent protection and bypass and output disconnect switches are
to be provided by the user. Table L lists the maximum rating for bypass and output circuit
breakers satisfying the criteria for both.
Table L. Maximum Bypass and Output Circuit Breaker Ratings
UPS Model
Output Voltage Rating
208V/220V 380V 400V 415V 480V
Eaton 9390-120/100
Eaton 9390-160/100
80% Rated 450A 225A 225A 200A 200A
100% Rated 350A 200A 175A 175A 150A
Eaton 9390-120/120
Eaton 9390-160/120
80% Rated 500A 300A 250A 250A 225A
100% Rated 450A 225A 200A 200A 175A
Eaton 9390-160/160
80% Rated 700A 350A 350A 350A 300A
100% Rated 600A 300A 300A 300A 250A
POWER WIRING INSTALLATION NOTES
011509C
164201604-5
8 of 15