Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F 162
FFiigguurree 8833.. 116644220011660044--55 PPoowweerr WWiirriinngg IInnssttaallllaattiioonn NNootteess ((CCoonnttiinnuueedd))
POWER WIRING INSTALLATION NOTES
011509 C
164201604-5
11 of 15
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
29.See Figure 82 for UPM terminal locations and Table H or Table I for
termination requirements.
30.Setup of the CAN Bridge Card for parallel operation must be performed by an authorized
Eaton Customer Service Engineer. Contact service to schedule a date.
31.For parallel system circuit breaker ratings, see appropriate information in Table N.
32.For parallel system ratings, see the appropriate information in Table O through Table Q.
Table N. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)
Circuit Breaker Ratings
UPM Model
Config-
uration
Output Voltage
208V/220V 380V/400V/415V 480V
MOB MIS MBP MOB MIS MBP MOB MIS MBP
9390-120/100
9390-160/100
1+1 500 500 500 250 250 250 200 200 200
2+0 and 2+1 500 1000 1000 250 500 500 200 400 400
3+0 and 3+1 500 1600 1600 250 800 800 200 600 600
4+0 500 2000 2000 250 1000 1000 200 800 800
9390-120/120
9390-160/120
1+1 500 500 500 250 250 250 200 200 200
2+0 and 2+1 500 1000 1000 250 500 500 200 400 400
3+0 and 3+1 500 1600 1600 250 800 800 200 600 600
4+0 500 2000 2000 250 1000 1000 200 800 800
9390-160/160
1+1 600 600 600 300 300 300 250 250 250
2+0 and 2+1 600 1200 1200 300 600 600 250 500 500
3+0 and 3+1 600 2000 2000 300 1000 1000 250 800 800
4+0 600 2400 2400 300 1200 1200 250 1000 1000
Installation Information