POWER WIRING INSTALLATION NOTES
011509 D
164201604-5
12 of 15
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
Table O. INPUT/OUTPUT Ratings for Eaton 9390-120/100 and 9390-160/100 Parallel Systems
Configu-
ration
Units Rating 50/60 Hz
Basic Unit Rating at 0.9 lagging pF load
kVA
kW
100
90
100
90
100
90
100
90
100
90
Input and Bypass Input
Output
VOLTS
VOLTS
208/220
208/220
380
380
400
400
415
415
480
480
All
AC Input from UPM
Full Load Curren t for each Module
(3) Phases, (1) Neutral-if required, (1) Ground
D
Amps 278/262 152 144 139 120
Minimu m Conducto r Size for each Modul e
Number per Phase for each Module
AWG or kcmil
(each)
See Table E through Table G for wire
size.
1+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps 278/262 152 144 139 120
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps 278/262 152 144 139 120
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
1/0
(1)
4
(1)
4
(1)
4
(1)
4
(1)
2+0
and
2+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps 556/524 304 288 278 240
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps 556/524 304 288 278 240
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
3/0
(1)
1/0
(1)
1/0
(1)
1/0
(1)
1/0
(1)
3+0
and
3+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps 834/786 456 432 417 360
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps 834/786 456 432 417 360
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
1/0
(2)
2/0
(1)
2/0
(1)
2/0
(1)
2/0
(1)
4+0
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps
1112/
1048
608 576 556 480
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps
1112/
1048
608 576 556 480
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
2/0
(2)
2/0
(1)
2/0
(1)
2/0
(1)
2/0
(1)
NOTE: Callout letters D, F, and G map to Figure 79 sheets 4, 5, and 6.