POWER WIRING INSTALLATION NOTES
011509 D
164201604-5
13 of 15
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
Table P. INPUT/OUTPUT Ratings for Eaton 9390-120/120 and 9390-160/120 Parallel Systems
Configu-
ration
Units Rating 50/60 Hz
Basic Unit Rating at 0.9 lagging pF load
kVA
kW
120
108
120
108
120
108
120
108
120
108
Input and Bypass Input
Output
VOLTS
VOLTS
208/220
208/220
380
380
400
400
415
415
480
480
All
AC Input from UPM
Full Load Curren t for each Module
(3) Phases, (1) Neutral-if required, (1) Ground
D
Amps 333/315 182 173 167 144
Minimu m Conducto r Size for each Modul e
Number per Phase for each Module
AWG or kcmil
(each)
See Table E through Table G for wire
size.
1+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps 333/315 182 173 167 144
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps 333/315 182 173 167 144
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
1/0
(1)
2
(1)
2
(1)
2
(1)
4
(1)
2+0
and
2+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps 666/630 364 346 334 288
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps 666/630 364 346 334 288
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
3/0
(1)
1/0
(1)
1/0
(1)
1/0
(1)
1/0
(1)
3+0
and
3+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps 999/945 546 519 501 432
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps 999/945 546 519 501 432
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
1/0
(2)
2/0
(1)
2/0
(1)
2/0
(1)
2/0
(1)
4+0
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps
1332/
1260
728 692 668 576
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps
1332/
1260
728 692 668 576
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
2/0
(2)
3/0
(1)
3/0
(1)
3/0
(1)
2/0
(1)
NOTE: Callout letters D, F, and G map to Figure 79 sheets 4, 5, and 6.