165 Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F
FFiigguurree 8833.. 116644220011660044--55 PPoowweerr WWiirriinngg IInnssttaallllaattiioonn NNootteess ((CCoonnttiinnuueedd))
POWER WIRING INSTALLATION NOTES
011509 D
164201604-5
14 of 15
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
Table Q. INPUT/OUTPUT Ratings for Eaton 9390-160/160 Parallel System
Configu-
ration
Units Rating 50/60 Hz
Basic Unit Rating at 0.9 lagging pF load
kVA
kW
160
144
160
144
160
144
160
144
160
144
Input and Bypass Input
Output
VOLTS
VOLTS
208/220
208/220
380
380
400
400
415
415
480
480
All
AC Input from UPM
Full Load Curren t for each Module
(3) Phases, (1) Neutral-if required, (1) Ground
D
Amps 444/420 243 231 223 193
Minimu m Conducto r Size for each Modul e
Number per Phase for each Module
AWG or kcmil
(each)
See Table E through Table G for wire
size.
1+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps 444/420 243 231 223 193
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps 444/420 243 231 223 193
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
2/0
(1)
1/0
(1)
1/0
(1)
1/0
(1)
2
(1)
2+0
and
2+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps 888/840 486 462 446 386
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps 888/840 486 462 446 386
System Neutral Bonding Jumper
Minimu m Conducto r Size
Numbe r(See Note 28)
-
AWG or kcmil
(each)
1/0
(2)
2/0
(1)
2/0
(1)
2/0
(1)
1/0
(1)
3+0
and
3+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps
1332/
1260
729 693 669 579
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps
1332/
1260
729 693 669 579
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
2/0
(2)
3/0
(1)
3/0
(1)
3/0
(1)
2/0
(1)
4+0
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral-if required, (1) Ground
F
Amps
1776/
1680
972 924 892 772
AC Output to Critical Load
Full Load Curren t
(3) Phases, (1) Neutral-if required, (1) Ground
G
Amps
1776/
1680
972 924 892 772
System Neutral Bonding Jumper
Minimu m Conducto r Size
Number (See Note 28)
-
AWG or kcmil
(each)
3/0
(2)
1/0
(2)
1/0
(2)
1/0
(2)
3/0
(1)
NOTE: Callout letters D, F, and G map to Figure 79 sheets 4, 5, and 6.