Parameter Description Setting range Default Menu path
Ack TripCmd Ack TripCmd 1..n, Assignment
List
-.- [Control
/Bkr
/Trip Manager]
Trigger1 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50P[1].TripCmd [Control
/Bkr
/Trip Manager]
Trigger2 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50P[2].TripCmd [Control
/Bkr
/Trip Manager]
Trigger3 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50P[3].TripCmd [Control
/Bkr
/Trip Manager]
Trigger4 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 51P[1].TripCmd [Control
/Bkr
/Trip Manager]
Trigger5 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 51P[2].TripCmd [Control
/Bkr
/Trip Manager]
Trigger6 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 51P[3].TripCmd [Control
/Bkr
/Trip Manager]
Trigger7 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50X[1].TripCmd [Control
/Bkr
/Trip Manager]
Trigger8 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50X[2].TripCmd [Control
/Bkr
/Trip Manager]
Trigger9 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 51X[1].TripCmd [Control
/Bkr
/Trip Manager]
Trigger10 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 51X[2].TripCmd [Control
/Bkr
/Trip Manager]