P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 146
Revision 002 User’s and Installation Guide
10 Product specifications
10.1 Model numbers
The UPS systems are housed in free-standing cabinets with safety shields behind the doors. The UPS
systems are available in 50/60 Hz with various output power ratings.
The following sections detail the input, output, environmental, and battery specifications for the UPS.
10.2 Single module specifications
10.2.1 UPS system input
10.2.2 UPS system output
Models Power Rating Frequency
Eaton 9395P 750 kVA 750 kVA PF 1.0 50/60 Hz
Eaton 9395P 900 kVA 900 kVA PF 0.92 50/60 Hz
Eaton 9395P 1000 kVA 1000 kVA PF 1.0 50/60 Hz
Eaton 9395P 1100 kVA 1100 kVA PF 1.0 50/60 Hz
Operating Input Voltage
(Nominal + –15%)
400 Vac for operation from 340 Vac to 460 Vac
Operating Input Frequency Range
±5 Hz
Operating Input Current
See Table 3-4 on page 19.
Reduced for Generator Adjustable
Input Current Harmonic Content
< 3% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 61000-4-5
Battery Voltage
480 Vdc
UPS Output Capacity 100% rated current
Output Voltage Regulation ±10% dynamic, ±1.5% steady state
Output Voltage Adjustment (Nominal +/–3%) 380 Vac nominal, adjustable from 368.6 Vac to 391.4 Vac
400 Vac nominal, adjustable from 388 Vac to 412 Vac
415 Vac nominal, adjustable from 402.5 Vac to 427.5 Vac