P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 64
Revision 002 User’s and Installation Guide
When installing internal wiring to X-Slot terminals, route the wiring through the internal
opening in the X-Slot communication bay.
For installation and setup of an X-Slot card, please contact Eaton Corporation.
To install wiring to connections:
1. If not already installed, install the LAN and telephone drops.
2. Unfasten the front door latch and swing the door open (see Figure 4-1 on page 31).
3. Remove the UPS cabinet interface entry plates to drill or punch holes (see Figure 4-4 on page 36).
4. Reinstall the interface entry plates.
5. Route and install the LAN, telephone, and other cables to the appropriate X-Slot cards. See
Figure 4-23 on page 60 and Figure 4-26 for X-Slot location.
6. Close the door and secure the latch.
7. Refer to the manual supplied with the X-Slot card for operator instructions.
Figure 4-26. X-Slot communication bays
1 X-Slot communications bay 1
2 X-Slot communications bay 2
3 X-Slot communications bay 3
4 X-Slot communications bay 4