P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 58
Revision 002 User’s and Installation Guide
4.9 Installing interface connections
WARNING
Hazardous voltages are present near the user interface terminal area if the UPS is not totally
disconnected.
4.9.1 TB1, TB2, and TB3 connections (other than TB1 battery interface
connections)
NOTE
Interface wiring must be installed from the top of the UPS cabinet.
To install wiring to connections:
1. Verify the UPS system is turned off and all power sources are disconnected. See Chapter 17: “UPS
operating instructions” for shutdown instructions.
2. Unfasten the front door latch and swing the door open (see Figure 4-1 on page 31).
3. Remove the door. Remove the retaining screw located inside the door at the bottom hinge pivot
point, then lift the door off. Retain the hardware for later use.
4. Terminal block TB3 is accessible on the left side of the X-Slot communication bay. To gain access to
terminal block TB1 and TB2 and the left interface entry conduit landing plates, remove the screws
securing the top protective cover panel and remove the panel. Retain the hardware for later use
(see Figure 4-5 on page 37).
5. Remove the interface entry conduit landing plates to drill or punch holes (see Figure 4-4 on
page 36).
6. Reinstall the entry plates and install the conduit.
WARNING
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the
mains is required.
7. To locate the appropriate terminals and review the wiring and termination requirements, see
Section 3.2.3 on page 23, Table 4-1 on page 62, and Figure 4-22 through Figure 4-24.
8. Route and connect the wiring.
9. If wiring TB1 battery interface connections, proceed to Section 4.9.2; if wiring the X-Slot
connections only, proceed to Section 4.9.3; otherwise, proceed to Step 10.
10. When all wiring is complete, reinstall the protective cover panel and secure with the cabinet
mounted screws.
11. Reinstall the front door and secure with the retained hardware.
12. Close the door and secure the latch.
13.