P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 13
Revision 002 User’s and Installation Guide
Table 3-3: Air conditioning or ventilation requirements during full load operation
Ventilation required for cooling air exhaust: approximately 920 liter/sec/250-300kVA unit, + 560 liter/sec
(ISBM).
Figure 3-1. UPS cabinet dimensions (front view)750-1100 kVA (750-900 kVA does not include UPM4)
Rating
Heat rejection
kW
Heat rejection
BTU / h x 1000
750 kVA 29.5 100.7
900 kVA 38.5 131.3
1000 kVA 39.1 133.8
1100 kVA 51.5 175.6
A 736 (UPM 4)
B 1704 (Cust. 1/0 + ISBM)
C 1872 (UPM 1-3)
AB C