P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 55
Revision 002 User’s and Installation Guide
Figure 4-19. UPS ISBM section power terminal detail BB - separate battery
4.8.2 Battery wiring
CAUTION
When sizing the battery system, do not exceed the internal battery charger capabilities. See
Chapter 23: “Product specifications” for maximum battery charger current.
NOTE
An installed FI-UPM is always designated as UPM 4.
To install wiring to connections:
1. Route the battery cables between the UPS ISBM section and the battery system or battery dis-
connect. See figure Figure 4-14 through Figure 4-19 and Figure 4-21 for wiring access information
and terminal locations.
2. If wiring the UPS for a common battery, proceed to step 3; if wiring for a separate battery, proceed
to step 5.