P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 31
Revision 002 User’s and Installation Guide
4 UPS system installation
4.1 Preliminary installation information
WARNING
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
Chapter 3: “UPS installation plan and unpacking” for cabinet dimensions, equipment weight,
wiring and terminal data, and installation notes.
Do not tilt the cabinet more than ±10° during installation.
The landing plates can be removed to add cable entry holes as required. Plate material is 16 gauge
steel (1.5 mm/0.06” thick).
If perforated floor tiles are required for ventilation, place them in front of the UPS.
4.2 Unloading the UPS cabinet from the pallet and
mechanical installation
The UPS ISBM and UPM sections are bolted to a wooden pallet supported by wood skids. To remove
the pallet and mechanically install the UPS, perform the following procedure:
WARNING
The UPS cabinet is heavy. See Table 3-1 on page 12 for weight of cabinets. If unloading
instructions are not closely followed, the cabinet may cause serious injury and equipment
damage.
Do not tilt cabinets more than 10° from vertical.
Lift the cabinet only with a forklift or damage may occur.
CAUTION
To prevent damage to the wiring channel and wiring in the UPM section base when lifting or
moving the cabinet:
Lift and move the 3 x UPM section using only the front or rear fork lift slots.
Verify that the fork lift forks are in a horizontal position before inserting them into the fork
lift slots. DO NOT angle fork slots upward.