P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 22
Revision 002 User’s and Installation Guide
Figure 5-15. Warning label
In a common battery system, single and multiple UPMs are powered from one common battery
source. In a separate battery system, multiple UPMs are each powered from separate battery sources.
A Field installed UPM (FI-UPM) is always designated as UPM 4.
Terminals E1 through E12 are bus bar mountings. See Table 5-5 for power cable terminations and
Table 5-6 for recommended installation parts not supplied by Eaton Corporation. Figure 4-7 on page 41
through Figure 4-10 on page 43 show the location of the power cable terminals inside the UPS.
Table 5-5:
UPS cabinet power cable/busbar terminations for the
9395P 750 kVA / 900 kVA and 1000 kVA / 1100 kVA
NOTE
Bypass terminations are not applicable to IOM configurations.
Terminal function Terminal Function
Tightening torque
Nm
Bolt size
AC input to UPS rectifier E1 Phase L1 80 (47) M12 (M10)
E2 Phase L2 80 (47) M12 (M10)
E3 Phase L3 80 (47) M12 (M10)
AC input to bypass E6 Phase L1 80 (47) M12 (M10)
E7 Phase L2 80 (47) M12 (M10)
E8 Phase L3 80 (47) M12 (M10)
AC output to critical load E9 Phase L1 80 (47) M12 (M10)
E10 Phase L2 80 (47) M12 (M10)
E11 Phase L3 80 (47) M12 (M10)
DC input from battery to UPS E4 Battery (+) 80 (47) M12 (M10)
E5 Battery (-) 80 (47) M12 (M10)
Input and output neutral E12 Neutral 80 (47) M12 (M10)
Customer ground Ground Ground 80 (47) M12 (M10)