P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 74
Revision 002 User’s and Installation Guide
Table 5-2: CAN Bridge Card wiring terminations
Figure 5-5. Distributed bypass Pull-Chain wiring without MOBs
Use twisted pair wiring between the UPS and MOB AUX contacts.
From
UPS 1 CAN Bridge Card
To
UPS 2 CAN Bridge Card
To
UPS 3 CAN Bridge Card
(if installed)
To
UPS 4 CAN Bridge Card
(if installed)
J3-8 (L) J3-8 (L) J3-8 (L) J3-8 (L)
J3-9(H) J3-9(H) J3-9(H) J3-9(H)
J3-10 (Shield) J3-10 (Shield) J3-10 (Shield) J3-10 (Shield)
From UPS 1 To UPS 2 To UPS 3 (if installed) To UPS 4 (if installed)
TB2-1
(Pull Chain)
TB2-1
(Pull Chain)
TB2-1
(Pull Chain)
TB2-1
(Pull Chain)