P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 48
Revision 002 User’s and Installation Guide
Figure 4-13. Distributed bypass wire length
Required parallel system wiring length must be equal to ensure approximately equal current
sharing when in Bypass mode. For proper operation the following must be true:
1A = 2A = 3A = 4A
1B = 2B = 3B = 4B
In order to save cabling costs, the following is also considered to be sufficient:
1A+1B=2A+2B=3A+3B=4A+4B
Any difference in wire length will result in decreased capacity of the UPS system while on
bypass. For example, a 10% difference between the longest and shortest wire lengths will result
in a decrease in bypass capacity of 10%. This may disable transfer to inverter.