P-164000477 9395P750 kVA / 900 kVA and 1000 kVA / 1100 kVA 28
Revision 002 User’s and Installation Guide
Do not tilt the UPS cabinet more than 10° from vertical or the cabinet may tip over.
3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3 m on each side for
removing the cabinet from the pallet.
The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of the unit.
Do not remove the debris shield until installation is complete.
4. Remove the protective covering from the cabinet.
5. Remove the packing material, and discard or recycle in a responsible manner.
6. After removing the protective covering, inspect the contents for any evidence of physical damage,
and compare each item with the Bill of Lading. If damage has occurred or shortages are evident,
contact your service representative immediately to determine the extent of the damage and its
impact upon further installation.
While waiting for installation, protect the unpacked cabinet from moisture, dust, and other
harmful contaminants. Failure to store and protect the UPS properly may void your warranty.