38 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
Table 16. Power Cable Conduit Requirements
UPS Model
Voltage
Terminal
Number of
Wires in Conduit
Minimum
Conduit
Trade Size
Number of
Conduits
Power Xpert 9395-
1100/1000
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 6
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 5
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3–1/2
6
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 5
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 5
Power Xpert 9395-
1100/11000
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 6
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 5
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3–1/2
6
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 5
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 5
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3–1/2
6
Power Xpert 9395-
1100/650
Power Xpert 9395-
1100/750
Power Xpert 9395-
1100/825
See Note 2
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 6
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 5
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3–1/2
6
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 5
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 5
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3–1/2
6
DC (All
ratings)
Battery (Positive, Negative, Ground)
See Note 1
NOTE 1 Select conduit taking into consideration the DC input wire sizes listed in Table 5 or Table 6, the DC terminations listed in
Table 13, type of battery installation, and requirements from NEC Table 4, Electrical Metallic Tubing (EMT).
NOTE 2 Because of the future upgradability to a fully rated 1100 kVA UPS with the addition of the FI-UPM, these conduit sizes are
specified for an 1100 kVA UPS.
NOTE 3 Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing: Refer to the notes at the bottom of Table 5 Input/Output Ratings and External Wiring Requirements.
External overcurrent protection and disconnect are not provided by this product, but are required by codes.
Refer to Table 5, Table 6, Table 7 or Table 8 for wiring requirements. If an output lockable disconnect is
required, it is to be supplied by the customer.
Table 17 lists the recommended rating for input circuit breakers.