52 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
4. Remove the screws securing the corner channel and remove the channel (see Figure 22). Retain the
hardware for later use.
Figure 20. Section Joining
Left Top Panel
Wireway Panel
Left Middle Panel
Corner Channel
UPM Section
Interior Left
Side Panel
5. Remove the screws securing the left top panel and remove the panel (see Figure 20). Retain the hardware
for later use.
6. Remove the screws securing the left middle panel and remove the panel (see Figure 20). Retain the
hardware for later use.
Use care during installation to protect components mounted on the right side of the ISBM section and the
intercabinet wiring harnesses attached to the left side UPM section from damage.
NOTE Clearance between the ISBM and the UPM sections must be less than 1/2” so that
joining brackets can be installed.
UPS System Installation