6 Parameter structure
6.4 Control signal terminals
136 DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com
6.4.2.10 P-12 = 10: SWD control
Table 42: P-12 = 10: SWD control
P-15
DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0 START No function Select AI1 REF/f-Fix1 AI1 REF
1 START Select AI1 REF/f-Fix Select f-Fix Bit0 AI1 REF
2 START Select f-Fix Bit0 Select f-Fix Bit1 Select f-Fix/f-max
3 START Select AI1 REF/f-Fix1 EXTFLT AI1 REF
4 START Select AI2 REF/AI1 REF AI2 REF AI1 REF
5 Not permissible
6 FWD No function EXTFLT AI1 REF
7
Not permissible
8 START No function Select f-Fix Bit0 Select f-Fix Bit1
9 Not permissible
10 Not permissible
11 Not permissible
12 Not permissible
13 START No function EXTFLT No function
14 Not permissible
15
1)
ENA No function Select Fire Mode/Normal OP No function
16
2)
ENA Select AI1/f-Fix2 Select Fire Mode/Normal OP AI1 REF
17 ENA Select f-Fix Bit0 Select Fire Mode/Normal OP Select f-Fix Bit1
1) If P-15 = 15 and fire mode is active, the drive will run with fixed frequency 4 (f-Fix4), which is set with P-13.
2) If P-15 = 16, the setpoint value selection will be independent from fire mode.