7 Technical Data
7.2 Specific rated operational data
162 DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com
7.2.1 DC1-S1… device series
Size Symbol Unit 7D0 011
Rated operational current I
e
A 7.0 10.5
Overload current for 60 s every 600 s i
l
A 10.5 16.5
Assigned motor output
PkW0.37 0.55
PHP0.5 0.75
Power side (primary side):
Number of phases single-
phase
single-
phase
Rated operating voltage U
LN
V 110 (-10 %) - 115 (+10 %)
48 - 62 Hz
99 - 126 ±0 %
Input current (phase current) I
LN
A 8.5 12.5
Switching frequency (pulse frequency)
Default Setting f
PWM
kHz 8 8
Setting range f
PWM
kHz 4 - 32 4 - 32
Maximum leakage current to earth (touch
current), at U
LN
: 120 V, without motor
I
Touch
mA 4.8 4.8
Efficiency η
0.95 0.95
Heat dissipation
At I
e
(150 %) P
V
W 63 103.4
During no-load running, standby
(locked, without fan)
P
V
W 3.07 3.07
Fan, built-in
1)
Construction size FS1 FS1
1) Not with IP66 degree of protection