Eaton PowerXL - Messages after a Data Transfer with a DX-COM-STICK2; Operating Status Indicators

Eaton PowerXL
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Parameter structure
6.5 Messages
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com 141
6.5.2 Messages after a data transfer with a DX-COM-STICK2
Table 46: Possible messages after a data transfer
6.5.3 Operating status indicators
The six flashing dots on the seven-segment display are used to indicate
various operating statuses.
4-20 F The analog input’s input current does not fall within the specified range.
Check the setting in P-16 for AI1 and P-47 for AI2
In the case of 4-20mA:
Check the setpoint connection for wire breakage
SC-FLt
Internal error
Please contact your nearest Eaton sales branch
FAVLty
Internal error
Please contact your nearest Eaton sales branch
Message Possible causes and fixes
View Description
PASS-r Parameter transfer to DX-COM-STICK2 was successful
OS-Loc DX-COM-STICK2 locked.
In order to transfer data, check the switch position on the side.
FAiL-r
Error while attempting to read the parameters from the variable frequency drive.
PASS-t Parameter transfer to variable frequency drive successful.
FAiL-P
The parameter set stored in the DX-COM-STICK2 is for a different rating (different motor
current, motor output, etc.) than that of the connected variable frequency drive.
Fail-t
Error when attempting to copy parameter set to variable frequency drive
no-dAt No data found in DX-COM-STICK2.
dr-Loc Parameter set in variable frequency drive locked. Unlock variable frequency drive first.
dr-rVn The variable frequency drive has an enable signal and cannot take new parameters.
Stop the variable frequency drive.
tyPE-E
The parameter set stored in the DX-COM-STICK2 does not match the variable frequency drive.
Only transfers from the variable frequency drive to the DX-COM-STICK2 are possible.
tyPE-F
The DX-COM-STICK2 is not compatible with the variable frequency drive.
8 . 8 . 8 . 8 . 8 . 8 .
1 2 3 4 5 6
Number(s) Behavior Meaning
1, 2, 3, 4, 5, 6 Flash synchronously Overload
The current current exceeds the value set with P-08.
1, 6
Flash in an alternating
pattern
Power outage or power supply switched off
1
flashes Fire Mode enabled