EasyManua.ls Logo

Eaton PowerXL - Configuration of the Control Signal Terminals

Eaton PowerXL
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Parameter structure
6.4 Control signal terminals
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com 127
6.4.2 Configuration of the control signal terminals
6.4.2.1 P-12 = 0: Terminal-based operation
Table 33: P-12 = 0: Terminal-based operation
The setpoint and the control commands are set/issued via terminals.
P-15 DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0 START No function Select AI1 REF/f-Fix1 AI1 REF
1 START Select AI1 REF/f-Fix Select f-Fix Bit0 AI1 REF
2 START Select f-Fix Bit0 Select f-Fix Bit1 Select f-Fix/f-max
3 START Select AI1 REF/f-Fix1 EXTFLT AI1 REF
4 START Select AI1 REF/AI2 REF AI2 REF AI1 REF
5 START Select Quickdec Select AI1 REF/f-Fix1 AI1 REF
6 START No function EXTFLT AI1 REF
7
START Select Quickdec EXTFLT AI1 REF
8 START No function Select f-Fix Bit0 Select f-Fix Bit1
9 START Select Quickdec Select f-Fix Bit0 Select f-Fix Bit1
10 Pulse START (NO) Pulse STOP (NC) Select AI1 REF/f-Fix1 AI1 REF
11 Pulse START (NO) Pulse STOP (NC) Select Quickdec AI1 REF
12 START Select Quickdec Select AI1 REF/f-Fix1 AI1 REF
13 START Select f-Fix Bit0 EXTFLT Select f-Fix Bit1
14 Pulse START (NO) Pulse STOP (NC) Select Quickdec Select DIG REF/f-Fix1
15 START Select f-Fix4/AI1 REF Select Fire Mode/Normal OP AI1 REF
16 START Select f-Fix4/f-Fix2 Select Fire Mode/Normal OP No function
17
START Select f-Fix Bit0 Select Fire Mode/Normal OP Select f-Fix Bit1

Table of Contents

Related product manuals