6 Parameter structure
6.4 Control signal terminals
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com 127
6.4.2 Configuration of the control signal terminals
6.4.2.1 P-12 = 0: Terminal-based operation
Table 33: P-12 = 0: Terminal-based operation
The setpoint and the control commands are set/issued via terminals.
P-15 DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0 START No function Select AI1 REF/f-Fix1 AI1 REF
1 START Select AI1 REF/f-Fix Select f-Fix Bit0 AI1 REF
2 START Select f-Fix Bit0 Select f-Fix Bit1 Select f-Fix/f-max
3 START Select AI1 REF/f-Fix1 EXTFLT AI1 REF
4 START Select AI1 REF/AI2 REF AI2 REF AI1 REF
5 START Select Quick‐dec Select AI1 REF/f-Fix1 AI1 REF
6 START No function EXTFLT AI1 REF
7
START Select Quick‐dec EXTFLT AI1 REF
8 START No function Select f-Fix Bit0 Select f-Fix Bit1
9 START Select Quick‐dec Select f-Fix Bit0 Select f-Fix Bit1
10 Pulse START (NO) Pulse STOP (NC) Select AI1 REF/f-Fix1 AI1 REF
11 Pulse START (NO) Pulse STOP (NC) Select Quick‐dec AI1 REF
12 START Select Quick‐dec Select AI1 REF/f-Fix1 AI1 REF
13 START Select f-Fix Bit0 EXTFLT Select f-Fix Bit1
14 Pulse START (NO) Pulse STOP (NC) Select Quick‐dec Select DIG REF/f-Fix1
15 START Select f-Fix4/AI1 REF Select Fire Mode/Normal OP AI1 REF
16 START Select f-Fix4/f-Fix2 Select Fire Mode/Normal OP No function
17
START Select f-Fix Bit0 Select Fire Mode/Normal OP Select f-Fix Bit1