System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
65
Schedule Sources
Parameter Setting
SA Num Type the number (from the Smart Alarm States table) of the Smart Alarm for
which this source is an input.
Status Set to Enabled.
First Activation Set to the date and time when the Schedule Source will activate for the first time
(see the diagram below).
Duration Set to the length of time that the Schedule Source will remain active each time it
activates (see the diagram below).
Interval Set to the time interval between the start of each activation (see the diagram
below).
Number of
Activations
Set the number of activations.
If set to zero then there is no limit to the number of activations.
Invert The source is inverted before it is used to trigger the Smart Alarm. The Smart
Alarm will be triggered when the source becomes inactive.
Trigger Specify how the source is used to trigger the Smart Alarm.
Level – triggered as long as the source is active.
Edge Set – triggered when the source becomes active.
Edge Reset – triggered when the source becomes inactive
Edge Latch – triggered when the source becomes active. The Smart Alarm
remains active as long as the source is active.
Scheduled Sources Operation
Duration
Interval
Active
Inactive
First
Date/Time
Time
1 2
3 4
Activation
number