Modbus Read, Write and Override Parameters plus Exception Codes
108 UDC2500 Universal Digital Limit ControllerProduct Manual 8/05
10.4.7 Display
Table 10-9 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Display.
Table 10-9 Set-up Group – Display
Parameter
Description
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Hex Decimal
Decimal Point
Location
009B 155 INT R/W
0 = XXXX – Fixed
1 = XXX.X – Floating
decimal point to one
2 = XX.XX – Floating
decimal point to two
Temperature
Units
0081 129 INT R/W
0 = °F
1 = °C
2 = None
Power
Frequency
00A6 166 INT R/W 0 = 60 Hertz
1 = 50 Hertz