Troubleshooting/Service
84 UDC2500 Universal Digital Limit ControllerProduct Manual 8/05
7.8 Restoring Factory Configuration
Introduction
This procedure restores the configuration of the instrument back to the Factory Settings
per Section 3.11.
ATTENTION: Restoring the factory configuration overwrites all user-entered
configuration changes. This procedure cannot be undone, it is a one-way process.
Table 7-11 explains how to restore Factory Configuration.
Table 7-11 Restoring Factory Configuration
Step What to do
1
Turn off the power to the instrument for at least five seconds.
2
Turn the power back on and simultaneously press the “FUNCTION” and
buttons.
This must be done while “TEST DONE” is being displayed.
3
If step 2 was performed correctly, the instrument will now display “UDC” [Upper]
“UPDATE” [Lower].
4
Press the Function Key. The instrument will now display “CFG” “RESTORE”
5
Press the Function Key. The instrument will now display “DOIN” “RESTORE”
6
When the instrument finishes the restore operation, it automatically resets itself and
restarts in the product mode. The instrument configuration will now be the same as it
was when the instrument left the factory and all user-entered configurations since that
time have been overwritten.