INSTALLATION
19/64
EN
4.2 Installation area
Before installation, make sure that the installation area satises the following requirements:
– operating temperature between +5°C and +45°C
– dry, frost resistant, well-ventilated
– no accumulation of heavy powders
– no high levels of humidity
– no atmospheric pollutants created by halogenated hydrocarbons (contained in solvents,
adhesives, aerosols, etc.)
– no atmospheric pollutants created by sulphurous gases
– no vibration.
WARNING
Danger of death caused by re!
Highly ammable materials or liquids can catch re
- do not use or store explosive or highly ammable substances (such as petrol, paint, paper,
wood, etc.) in the installation area of the appliance
- do not dry clothing within the boiler installation area
- do not use the equipment in an explosive atmosphere.
CAUTION
Flammable materials or liquids should not be stored or used near the burner.
IMPORTANT INFORMATION
Failure to observe these instructions will invalidate the warranty with respect to any damages
caused by any of these causes.
4.2.1 Flue gas system
Before installation, check the design suitability of the combustion ue system with respect to the
type of boiler to be installed and with respect to the applicable standards and regulations.
CAUTION
Operators should explain to the proprietor and person responsible for the domestic heating
system the burner is installed on, the importance of ensuring good inow of combustion air
and combustion product evacuation. They should also highlight that no modication should be
made to the heating system (comprised of air intake, burner, boiler and ue pipe) that could
alter the correct operation of the system.