COMMISSIONING
37/64
EN
5.4.1
Air ap position
Turn the hex key (1) supplied:
clockwise to increase the air ap opening (O2 rises, CO2 decreases).
counterclockwise to reduce the air ap opening (O2 decreases, CO2 rises).
O
2
+
CO
2
-
O
2
-
CO
2
+
1
Fig. 33
5.5 Adjusting burner output
2
4
1
8
7
65
3
1
Fuel-oil solenoid valve
2
Solenoid valve electrical connection
3
Fuel delivery pipe
4
Vacuum port pressure gauge connection
5
Suction connection
6
Return connection
7
Oil pressure regulator
8
Oil pressure gauge connection
Fig. 34
WARNING
Continuously check CO, CO2 and soot emissions when adjusting the output of the burner. CO
must not exceed 50 ppm.
WARNING