9MA10011 17/52
4.4.2 Analogue alarms
Thismenushowsthelistofonboardanalogueinputs.
4.4.2 ANALOGUEALARMS
01 ONBOARD-P1 |
02 ONBOARD-P2 |
03 ONBOARD-P3 |
04 ONBOARD-P4 |
05 ONBOARD-P5 |
06 ONBOARD-P6 |
07 ONBOARD-P7 |
08 ONBOARD-P8
SelecttherequiredanalogueinputusingtheUPandDOWNkeysandpressOK.
Apagedisplayingthefollowinginformationwillopen:
(exampleIndex01Input,pressureprobe)
4.4.2 ANALOGUEALARMS
Index 1/8 |
Name ONBOARD-P1 |
AlarmOutput 1 |
Delay(min) 0 |
Positiv.Emerg. 10.0 |
Positiv.Delay 8.0 |
Negativ.Emerg. 0.0 |
Negativ.Delay 0.0 |
AlarmHysteresis 0.1
• Index:InputIndex***
• Name:NameofInput***
• Alarm Output:0=noneassociated;1=Output1;
• Delay (min):minutesdelaybeforeactivatingAlarmOutput[0…240min]
• Positiv. Emerg: upper threshold and immediate generation of alarm when
limitexceeded
• Positiv. Delay:upperthresholdanddelayedgenerationofalarmwhenlimit
exceeded
- NOTE:Positiv.Emerg.>Positiv.Delay
• Negativ. Delay:lowerthresholdanddelayedgenerationofalarmwhenlower
limitexceeded
• Negativ. Emergency: lower threshold and immediate generation of alarm
whenlowerlimitexceeded
- NOTE:Negativ.Emerg.<Positiv.Delay
• Alarm Hysteresis:Alarmresethysteresis.
***Read-onlyinformation.
Notice : alarm thresholds and hysteresis values are expressed in the units of
measurelistedabove(point4.4.1fortheAnalogueInput).