9MA10011 9/52
2.3.1.1 Analogue inputs display
Allanalogueinputsareshownwiththefollowinginformation:
• NameofanalogueinputP1,P2,…P8**.
- ONBOARD Px if the resource is integrated (see section 4.4 Onboard
Resources).
- PxforTelevisnetworkresources(seesection4.5Network1).
• Value(2gureswithdecimalpointindicatingtenthsofadegree)orProbeError.
• Unitofmeasure(Cdegreescentigrade;Barpressureinbar;etc.).
• Alarmcondition.
2.3.1.2 Digital input display
Alldigitalinputsareshownwiththefollowinginformation:
• NameofdigitalinputD1,D2**.
- ONBOARD Dx if the resource is integrated (see section 4.4 Onboard
Resources).
- DxforTelevisnetworkresources(seesection4.5Network1).
• State(active/notactive).
• Alarmcondition.
**Thenumberofresourcesdependsonthesystemsettingsandmodel.
2.3.1.3 First switch on
Thispageappearswhenthedeviceisswitchedonforthersttime.
Afterthis,youcanaccessthismenufrommenu4-StandardConguration
(sub-menu4.0FirstSwitchOnand“force”theFirstSwitchOnfunction.
* FIRST SWITCH ON *
Language English |
AAAA/MM/GG: <date> |
HH:MM:SS: <hour> |
PeriodREC. min:000 |
EN12830: <=24h/30s |
Num.ofprobesused: 8 |
Num.ofdigitsused: 2
It is highly recommended to congure:
• Date(yy/mm/dd)formatandtime(hh:mm/ss).
• Recordingperiod,expressedinminutes.
ValueRECperiod
000 30seconds
001 1minute
002 2minutes
… …
099 99minutes
100 100minutes
Basedontherecordingperiodset,linebelowshowsthedegreeofconformitywith
UNIEN12830inrealtime.