9MA10011 44/52
12. APPLICABLE STANDARDS
12.1 European Community Directives
TheproductcomplieswiththefollowingEuropeanCommunityDirectives:
•CouncilDirective2006/95/EC
•CouncilDirective2004/108/EC
and complies with the following harmonised regulations: EN 61010-1 & EN
61326-1
EliwellmonitoringsystemsintheMemory1000family:
CanbeusedinEN12830-compliantapplications.
12.1.1 EN12830 compatibility
Memory1000iscapableofrecordingtemperaturesasperEN12830regulationat
thefollowingconditions:
• recordingintervalmustbeset<=30minutes
• onboardprobesmustbeperformedwithEliwellNTCprobes
• TelevisnetworkresourcesmustbeprovidedwithEliwellNTCprobes
NOTE,FORPRINTERENABLEMODELSONLY:recordingofthetemperaturesfrom
resourcesintheTelevisnetworkissuspendedwhileprinting.Inordertoguarantee
therecordingsaccordingtoEN12830itissuggestedtooperateasfollowing:seta
recordingintervalof15minutesand,afteraprintprocessisterminated,waitat
least20minutesbeforerunninganewprintprocess.
12.1.2
Limitation to the recording frequency for the Televis network resources
Incaseofrecordingintervalsshorterthan15minutes,thehistoryoftheresources
in the Televis network may present missing recording due to communication
errors(e.g.fordisturbancestothecommunicationlineindependentthanMemory
1000)orbecauseoftherecordingsaresuspendedduringtheprintprocesses.
12.2 Application information sheet
12.2.1 Type of data logging
Suitableforstorage.
12.2.2 General Requirements
Measurement range
• Onboardprobes:-40…+105°C.
• Networkdevices:UseonlyclassIIrateddevices(Eliwell).
Protection rating provided by outer casings
• IP20.
Supply voltage and frequency
•230Va+10%50/60Hz±3Hz.
•230Va-15%50/60Hz±3Hz.
Power failures
Non-volatileinternalmemory,10-yearduration.