Loading...
9MA10011 48/52
Name
Part number
Description NOTE
Pressure transducers
EWPA030
TD200130
EWPA030
4...20mA
0/30barpressure
transducerwith
maleconnector
Setthefollowing
parameters:
for04mA=0
for20mA=30
Seepar 4.4.1
TD200030
EWPA030
4...20mA
0/30barpressure
transducerwith
femaleconnector
Setthefollowing
parameters:
for04mA=0
for20mA=30
See par 4.4.1
EWPA007
TD200107
EWPA007
4...20mA
-5/8barpressure
transducerwith
maleconnector
Setthefollowing
parameters:
for04mA=-0.5
for20mA=7
See par 4.4.1
TD300008
EWPA007
4...20mA
-5/8barpressure
transducerwith
femaleconnector
Setthefollowing
parameters:
for04mA=-0.5
for20mA=7
See par 4.4.1
Humidity transducers
EWHS280 SN560000
Relativehumidity
transducer
(measurement
range15%...90%)
Setthefollowing
parameters:
for04mA=20
for20mA=100
See par 4.4.1
Name
Part number
Description NOTE
EWHS300 SN520000
Relativehumidity
transducer
(measurement
range0%...100%)
Setthefollowing
parameters:
for04mA=0
for20mA=100
See par 4.4.1
EWHS310-2 SN510010
Humidity(range
0%...100%)and
temperature
(Range-30°C…
+70°C)
transducers
Setthefollowing
parameters:
for04mA=20
for20mA=100
See par 4.4.1
RS485 connectivity modules
130TTL
RS485bus
adapter
BA11250N3700
Communication
interface
TTL/RS-485
12Vaux.output
forpowersupply
todevice
TTLcable,L=
1m(
2
)
150TTL
RS485bus
adapter
BA10000R3700
Communication
interface
TTL/RS-485
TTLcable,L=
1m(
2
)