BA-en-3041-2008_PC 25
Due to the power consumption of the high voltage generator, the cable cross-
sections should be as large and the cables as short as possible in order to
reduce cable loss.
The voltage at the individual contacts must not exceed 60 V DC.
3.8.2 Connecting the supply voltage 90 - 264 V AC
The 90–264 V AC power supply is connected via the standard C13 device
plug.
Caution!
In case of customer’s provision:
To prevent an interruption of the power supply due to vibrations or other
mechanical influences, Eltex recommends using a plug for power cable,
form C13 with integrated locking, see Chapter 10 "Spare parts and accesso-
ries”, page 81.
3.9 Field bus Interface
Warning!
Electric shock hazard!
Work may be carried out only if:
the supply voltage to the generator has been disconnected
the machine is at a standstill because the bars pick up charges if the
material web is running.
Caution!
The voltage at the individual contacts must not exceed 60 V DC.
Fig. 13:
Connector pin
assignment
90 - 264 V AC
plug
wire color
1 L brown or black
2 N blue or black
3 PE yellow/green
F00059
3
1
2