26 BA-en-3041-2008_PC
3.9.1 CANopen® (optional)
The generators POWER CHARGER PC_ _ support the standardized
CANopen® protocol according to CiA 301. The generator logs onto the
network as a slave with the device profile 401 for input/output devices.
The following CANopen® services are supported:
Emergency Protokoll (EMCY) for the transmission of error and warning
events
Heartbeat Producer for node monitoring
Static mapping for PDO transfer
All important data are available in PDOs.
Prompt SDO transfer
Segmented transfers and block transfers are not supported.
CANopen®
objects for storing und restoring parameter data
LSS services for setting the node address and baud rate (see chapters
4.4 and 4.5).
The complete description of the CANopen® protocol for the generator
POWER CHARGER PC_ _ and the corresponding EDS file "PC.eds" are
available in the download area: www.eltex.com/support/download
service.
The bus network has to be terminated at both sides.
Connector pin assignment CANopen®
Plug connector M12x1 A-coded
Caution!
For the variant with CANopen®, a cable suitable for CAN bus networks
with a surge resistance of 120 ohms must be used for both bus leads; this
is the only way to ensure the proper functioning of the CAN network.
The maximum cable lengths specified in CiA 303-1 as a factor of the
transmission speed must be observed for the whole network and for the
individual spur lines.
Fig. 14:
Connector pin
assignment
CAN-Bus female/
male
wire color
1 Shield
2 NC red
3 GND-Bus black
4 CAN-H white
5 CAN-L blue
Plug housing: Shield
Socket female Plug male
F00052y + F00053y