Figure 3-41: Fieldbus Device List
3.19 Power and connect to a FOUNDATION fieldbus
device
The Trex unit can power one FOUNDATION fieldbus device. The Trex unit can provide
approximately 10 volts at 25 mA to power a FOUNDATION fieldbus device. (The Trex unit
will draw approximately 12 mA when it is online).
If you try to apply power from the Trex unit when the device is externally-powered, the
Field Communicator application prevents the Trex unit from supplying power. This
protects the Trex unit from damage.
Note
When the Trex unit powers a FOUNDATION fieldbus device, two internal terminators and a
power conditioner are applied. Ensure the device is not connected to a fieldbus segment,
even if the segment is unpowered.
User Guide Field Communicator application
September 2021
User Guide 105