10 DIN IPG215D Panel Mounting and Wiring Panel Mounting and Wiring • 11
2.1.3 10 DIN Panel Pressure Transducer and Voltage Input Wiring
Emerson Pressure Transducer
The 851-4445 panel provides analog inputs factory-wired to a terminal block on the panel back plate for easy connection
of input sensors. Figure 2-5 shows wiring detail for connecting Emerson pressure transducers, applicable for part
numbers 800-2100, 800-2200, and 800-2500. Connect the white signal wire from the sensor lead to the Pb1 connection,
connect the black ground to the GND pin 8, connect the red power source wire to the +5V pin 15 terminal. Connect the
sensor cable shield wire to earth ground by attaching to the panel back plate. If the Emerson pressure transducer wiring
must be extended beyond the factory leads, then Emerson specifies P/N 135-8771 22/3 shielded cable.
Figure 2-4 - 10 DIN Panel Temperature Sensor Wiring