62 Chapter 6 Application Of INTELLISLOT
Liebert. PEX+Series Precision Air Conditioner User Manual
Figure 6-10 Configuration interface
3. Click Access under SNMP at the left side of the interface, as shown in Figure 6-11. Type the user name ‘Liebert’
and the password ‘Liebert’, and click OK to enter the configuration interface.
Note
The user name and password are case-sensitive.
Figure 6-11 Typing user name and password
4. Configure the Network Management System (NMS) of the host monitoring center in Figure 6-12. Click Edit and type
the IP address of the NMS in IP Address. Select read or write, type ‘Public’ in Community and then click Save.
Note
Before setting the NMS, the Edit button is displayed on the interface. After the configuration is edited, the Edit
button will become the Save button.
After the NMS is configured, you must click Save to save the configuration.
Password
Username
OK Cancel